APC ACRC301S User's Guide Page 18

  • Download
  • Add to my manuals
  • Print
  • Page
    / 60
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 17
Operation: Control the Environment
12 InfraStruXure InRow RC—Operation and Maintenance
How to tune the PIDs
A qualified service technician must tune the PID loop to optimize the performance of the cooling group.
1. Adjust the integral and derivative constants to zero, and the proportional constant to 0.7.
2. Set the temperature setpoint value and start the cooling group.
3. When the temperature reaches a stable value, increase the proportional constant by 0.5. If the
temperature does not respond to this change, adjust the setpoint.
4. Repeat step 3 until the temperature value starts to oscillate and the peak amplitude of the
oscillations is constant.
5. Note the time, in minutes, between the peaks of the oscillations. This is the Ultimate Period, P
U.
6. Note the value of the proportional constant. This is the Ultimate Gain, G
U.
7. Compute the PID constants using the table below. Select the type of control from the rows of the
table, and use the equations in the columns to compute the values for each constant.
8. Set each constant according to these calculations.
You may need to further tune the PID loop in the following ways to account for changes in the room load:
Caution
The PID loop must be tuned after the equipment in the room is installed and running. The
loop should be tuned periodically to account for changes in the room load.
Control Method Proportional Integral Derivative
P0.5*G
U
––
P + I 0.45*G
U
0.54*G
U
/P
U
P + I + D 0.6*G
U
1.2*G
U
/P
U
0.075*G
U
*P
U
Loop Behavior PID Tuning Correction
Slow response to temperature changes Increase the proportional multiplier or increase the
derivative multiplier.
Over-cooling/under-cooling after changes in
the room load or changes in setpoint
Increase the derivative or the proportional multipliers.
Environmental temperature never reaches
the setpoint
Increase the integral setting.
Over-cooling/under-cooling on constant
room load
Decrease the integral multiplier.
Page view 17
1 2 ... 13 14 15 16 17 18 19 20 21 22 23 ... 59 60

Comments to this Manuals

No comments