MX06 Power Plant User’s Manual Page 11
3.6. Load Protection Installation
Circuit Breaker Installation
Standard circuit breaker output boards are available with two 30 Amp breakers or one 60 Amp
breaker. Output boards are installed at the factory and are not field replaceable units. Contact
APC if the output configuration is not suitable for your needs. Other breaker sizes are not
available.
GMT Fuse Installation
Fuse holders that accommodate GMT fuses are located on the front panel on the left side of the
unit. Insert the fuse in the holder; observing the tripped indicator is correctly oriented. Use the
chart shown in Figure 3.6-1 to help determine what size fuses will carry the desired current.
When using several of the larger GMT fuses in one shelf, better heat dissipation will be
achieved if the fuses are spaced out evenly within the output panel. A list of GMT type fuses
available from APC is provided in Figure 3.6-2.
AMBIENT TEMPERATURE
20° C 50° C 60° C
7.5 Amp 5 Amp 4.5 Amp 4 Amp
10 Amp 7 Amp 6 Amp 5 Amp
FUSE
SIZE
15 Amp 10 Amp 9 Amp 8 Amp
Figure 3.6-1 GMT Fuse Temperature De-rating Chart
GMT Fuses
FUSE RATING PART NUMBER FUSE RATING PART NUMBER
¼ Amp FFA-0030 3 Amp FFA-0036
½ Amp FFA-0031 5 Amp FFA-0037
3/4 Amp FFA-0032 7½ Amp FFA-0029
1 Amp FFA-0033 10 Amp FFA-0038
1¼ Amp FFA-0039 15 Amp FFA-0040
1½ Amp FFA-0035
Figure 3.6-2 GMT fuses available from APC