MX06 Power Plant User’s Manual Page 21
5 Operation
5.1. Description
The MX06 is designed for years of operation with no user input. The power system is pre-set at
the factory with all parameters needed for normal operation. The front panel LEDs and the
alarm output relays, indicate the general health of the unit.
Voltage adjustments or changes to switch settings on the system Controller Board are only
required under the follow conditions:
Rectifiers are added or removed from the original configuration shipped from the factory.
Modifications are required to the User Alarm Input settings (alarm priority or input contact
sense).
Voltage threshold levels for alarm conditions or motorized breaker control need to be
changed from the factory default settings.
5.2. MX06 Operation
The control card for the MX06-50 is different than the control card for the MX06-100 due to
increased number of rectifiers in the MX06-100. The control card for the MX06 is the 0P9172
and for the MX06-100, the control card is the 0P9745. This section will deal with configurations
applicable to all MX06 power systems.
MX06 Voltage Adjustments
Power plant voltage level is the only adjustment required on a standard MX06. This is
performed using the “V ADJ” potentiometer on the front panel of the Control / Distribution
module. The voltage level should be set to accommodate the float voltage required by the
battery being used in the power system. Consult the battery manufacturer’s data sheet to get
the operating voltage information.