MX06 Power Plant User’s Manual Page 12
3.7. Load Connections
Cable Size Considerations
The DC load cable(s) should be sized to limit the voltage drop from the DC power plant to the
loads per system design requirements. The cable(s) must also carry the full load current during
battery operation. During battery operation the voltage will be lower and for constant power
loads, the current will typically be higher. If assistance is required to determine the necessary
cables for the application, contact your sales representative or APC.
Circuit Breaker Protected Load Connections (30 or 60 Amps)
The circuit breaker lug landing connection provides a pair of #10-32 studs on 5/8” centers for
mounting two-hole lugs. A ring size of 0.221 in (5.6 mm) may also be used. Load Connections
should be made as shown in Figure 3.7-1.
Figure 3.7-1 Connections to Circuit Breakers