MX06 Power Plant User’s Manual Page 7
3.4. Battery Connections
WARNING: Hazardous energy levels are present on bare conductors in
the -48VDC distribution connection area of the plant. Accidental shorting of
distribution conductors can cause arcing and high currents that can cause
serious burns or other physical harm. It is recommended that:
Remove any jewelry, rings or watches while working on this
equipment.
Use insulated wrenches, screwdrivers, cutters, pliers and other tools.
Planning the Battery installation
The battery cable(s) should be sized to limit the voltage drop from the DC power plant to the
battery during charging per system design requirements. The cable(s) must also carry the full
load current during battery operation. If assistance is required to determine the necessary
cables for the application, contact your sales representative or APC (Refer to Chapter 7 for APC
Customer Support information.
An external fuse or circuit breaker (various options are available from APC) is recommended in
the negative line (located at the battery end) to protect the cables from the battery to the DC
power plant. The power plant can monitor auxiliary contacts from this breaker.
Connecting the Battery Cables
WARNING: Make certain that the battery polarity is correct when making
connections to the DC power plant. Incorrect connection could cause
severe equipment damage.
The battery cable connections are located at the rear of the unit as shown in Figure 3.4-1. The
battery positive and battery negative buses each provide a pair of #10-32 studs on 5/8” centers
for connecting two-hole battery cable lugs. A ring size of 0.221 in (5.6 mm) may also be used.
Connect the battery cables as applicable using #10-32 nuts. Cover all battery connections with
heat shrink after assembly.