MX06 Power Plant User’s Manual Page 29
6.3. Controls and Indicators
TWF0500H5401 Rectifier
FAIL LED DC output voltage below (-) 39.5 Volts DC or above
(-) 59.5 Volts DC.
MX06 Controller
Voltage Good LED (Green) On when voltage is between 50 and 57 Volts.
Major (Red) On when Major Relay is energized
Minor (Yellow) On when Minor Relay is energized
Low V LED 1 (Yellow) On when voltage is below 50 Volts DC.
Very Low V LED (Red) On when voltage is below 44 Volts DC.
6.4. Mechanical
TWF0500H5401 Rectifier
Dimensions 5 in (12.7 cm) high x 2-3/4 in (7cm) wide x 10.5 in (26.7 cm
deep
Weight 4 lbs (1.8 Kg)
Color Grey Front, Yellow zinc sides and back
Mounting Hot Swappable