USER’S GUIDE
Switched Rack PDU
12
Load indicator LED
The load indicator LED identifies overload and warning conditions for the displayed
phase or bank.
Watchdog Features
Overview
To detect internal problems and recover from unanticipated inputs, the Rack PDU uses
internal, system-wide watchdog mechanisms. When it restarts itself to recover from an
internal problem, a System: Warmstart event is recorded in the event log.
Network interface watchdog mechanism
The Rack PDU implements internal watchdog mechanisms to protect itself from
becoming inaccessible over the network. For example, if the Rack PDU does not
receive any network traffic for 9.5 minutes (either direct traffic, such as SNMP, or
broadcast traffic, such as an Address Resolution Protocol [ARP] request), it assumes
that there is a problem with its network interface and restarts itself.
Condition Description
Solid Green The current of the displayed phase or bank is under normal
conditions and is between Near Lowload and Near Overload
thresholds.
Yellow The displayed phase or bank is in a Near Overload Warning
condition. The current is above the Near Overload Warning
threshold.
Red The displayed phase or bank is in an Overload condition. The
current is above the Overload Alarm threshold.