APC SYPM2KU User Manual Page 13

  • Download
  • Add to my manuals
  • Print
  • Page
    / 22
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 12
13
For more information about all APC products, go to www.apcc.com
Regional availability: North America; South America
Regional availability: Middle East;
Asia; Africa; Australia; South America
Symmetra Rack-mount 208 VAC (Output) 120; 208 VAC (Output) 220; 230; 240 VAC (Output)
System Part No. SYH2K6RMT SYH4K6RMT SYH6K6RMT SYH2K6RMT-P1 SYH4K6RMT-P1 SYH6K6RMT-P1 SYH2K6RMI SYH4K6RMI SYH6K6RMI
Output
Capacity 2kVA/1.4kW 4kVA/2.8kW 6kVA/4.2kW 2kVA/1.4kW 4kVA/2.8kW 6kVA/4.2kW 2kVA/1.4kW 4kVA/2.8kW 6kVA/4.2kW
Output Voltage 208 (240 configurable) 120; 208 220; 230; 240
Max Configurable Power
with additional Power Modules 6kVA/4.2kW 6kVA/4.2kW (max 5kVA of 120VAC) 6kVA/4.2kW
Output Connections (2) NEMA L6-20R, (1) NEMA L6-30R (2) NEMA L6-20R, (12) NEMA 5-20R* (8) IEC 320 C13; (2) IEC 320 C19
Efficiency at full load 89% 85% 89%
By pass Internal Bypass (Automatic & Manual)
Output voltage Distortion typically <5% at full load (linear or non-linear)
Output frequency (synched to mains) 57-63 Hz 47-53 Hz
Output frequency (not synched) 60 Hz 50 Hz
Crest Factor up to 5:1
Input
Nominal input Voltage 208 or 240 208 220; 230 ; 240
Input Frequency 50/60 Hz +/- 5 Hz (auto-sensing)
Input Connection NEMA L6-30P Hardwire (3-wire)
Input Voltage range 155-276 V at 100% load
Input Power Factor at full load 0.98
Batteries
Battery Type Maintenance-free, sealed lead-acid battery with suspended electrolyte; leakproof.
Typical recharge time 4 hours
Replacement Battery Module (1) SYBT2 (2) SYBT2 (3) SYBT2 (1) SYBT2 (2) SYBT2 (3) SYBT2 (1) SYBT2 (2) SYBT2 (3) SYBT2
Communications and Management
Interface port DB-9; RS-232; Smart-Slot Card (2)
Management Software included PowerChute Network Shutdown; Web/SNMP Management Card ships standard with each unit
Control panel Multi-function LCD status & control console in multiple languages
Audible Alarm Alarm when on-battery; distinctive low battery alarm; configurable delays
Emergency Power Off (EPO) Yes
Physical
Dimensions HxWxD** (in/cm) 8U/14x19x27.25in /35.6x48.3x69.2cm 10U/17.5x19x27.25in/44.5x48.3x69.2cm 8U/14x19x27.25in/35.6x48.3x69.2cm
Weight net (lbs/kg) 164lb/74.5kg 229lb/104.1kg 294lbs/133.6kg 259lb/118kg 324lb/155kg 389lb/177kg 164lb/74.5kg 229lb/104.1kg 294lbs/133.6kg
Weight shipping 185lb/84.1kg 256lb/116.4kg 327lb/148kg 295lb/134kg 366lb/166kg 437lb/199kg 185lb/84.1kg 256lb/116.4kg 327lb/148kg
Environmental
Operating Temperature 0-40 C/ 32-104 F
Operating Relative humidity 0-95%
Operating Elevation 0-10000 feet/ 0-3000m
Storage Temperature -15 to 45C/ 5 to 113F
Storage Relative Humidity 0-95%
Storage Elevation 0-50,000 feet/0-15,000m
Audible noise at 3 feet (1 m) 60dBA
On-line thermal dissipation (BTU/hr) 590 1181 1771 843 1686 2529 590 1181 2529
Conformance
Approvals CSA; FCC A; UL 1778 C-tick; EN 50091-2; VDE
Warranty & Service Options
Warranty 2 years, repair or replace (1 year for battery modules in India)
"T" level for Service Option pricing T6 T6 T6 T6 T6 T6 T8 T8 T8
*Also referred to as 5-20RA (Canada) or T-Slot, and can be used as both 5-15R or 5-20R.
**Depth is measured from the front rail to the rear of the unit.
Symmetra
Rack-mount Product Specifications
Page view 12
1 2 ... 8 9 10 11 12 13 14 15 16 17 18 ... 21 22