Chapter 3. UPS configurations for cluster 63
Figure 65. UPS Shutdown Parameters window
4. On the Shutdown Parameters window, enter the following parameters:
UPS Low Battery Signal Time: This condition will occur if the battery is
very old and the UPS can supply power for a short period only (thus
immediate actions are required). It is the minimum number of minutes of
battery run time that the UPS needs to perform the essential tasks of a safe
system shutdown. Possible values are 2, 5, 7, and 10 minutes. We
recommend 10 minutes to get enough time for shutdown.
UPS Turn Off Delay: This period of time begins at power loss. After this
interval, the UPS turns off its output power (independent of any shutdown
completion). If line voltage returns during this period, turnoff of output
power is canceled (again independent of any shutdown operations in
progress). Possible delay values are 20, 180, 300, and 600 seconds. We
recommend to set the value as estimated in the time line (Figure 19 on
page 28).
UPS Wakeup Delay (Time): This is the time that the UPS must be
connected to a functioning power line before the attached systems can be
powered up. Possible delay values are 0, 60, 180, and 300 seconds.
Again, we recommend the maximum value of 300 seconds (to avoid
system boot in situations with short-time power return only). Additionally, a
percentage of full capacity for recharge may be specified as UPS Wakeup
Delay (Capacity).
Once you have set the parameters, click the OK button.
5. In the PowerChute PLUS main window (Figure 64 on page 62), select
Configuration > Application Shutdown Parameters. Figure 66 will be
displayed.