64 Implementing UPS Configurations with Microsoft Cluster Server
Figure 66. Double UPS Application Shutdown Parameters window
6. Disable the application shutdown (because this will be handled by the
command file UPS.CMD) and click the OK button.
7. In the PowerChute PLUS main window (Figure 64 on page 62), select
Configuration > Event Actions. Figure 67 will be displayed.
Figure 67. Double UPS Run Command File UPS On Battery
8. In the Event Actions window, select UPS On Battery.
a. Check the Run Command File checkbox and click Options. In the pop-up
window, insert the following in the Command File field:
“C:\UPS_CMD\UPS.CMD” UPSOnBattery >> C:\UPS_CMD\LOG.TXT
b. Set the Wait value to 5 seconds. This wait time (UPS On Battery Delay in
Figure 19 on page 28) before the command file is executed prevents short
power failures from shutting down the cluster. Click the OK button to apply
your choices.