66 APC NetworkAIR CM Series: Guidelines for Installation
When using a forklift to move the unit, use the shipping skid to protect the
bottom of the unit. When using chains, cables or rope to lift the unit, use
spreader bars to prevent damage to the finished panel.
Utility connections All connections are made through the bottom left of the unit for ease of
service connections. Refer to the installation manual for pipe sizes and
specific locations for your unit.
Power unit The CM unit uses either 1-phase or 3-phase power for operation depending
on the unit. Bring the service cable through the bottom left of the unit and
through the bulkhead hole into the electrical box to the circuit breaker
provided on the left side of the electrical box. The ground lug is located near
the high-voltage connector. THE UNIT MUST BE UTILITY
GROUNDED OR THE WARRANTY IS VOID.
Humidifier
connections
The humidifier inlet connection is in the bottom of the mechanical section. A
1/4" compression connection is supplied with the unit.
Condensate drain Condensate from the evaporator pan and discharge from the humidifier
flushing system drain through a 7/8" ID drain trap in the bottom of the unit.
Water supply to
humidifier
1. The humidifier fill valve orifice is sized for supply water pressure from
30 PSIG (210 kPa) to 85 PSIG (590 kPa).
2. For cases above 90 PSIG (630 kPa), install a pressure-reducing valve in
the water feed line to the unit.
3. With extremely dirty or muddy water sources, proper filtration is
required on the units incoming water line.
4. DO NOT use softened water with the humidifier. Softened water is too
conductive.
5. DO NOT use completely demineralized water with the humidifier. The
minerals allow the electrode principle to work.
6. DO NOT use a hot water source. Doing so will cause deposits that will
eventually block the fill valve orifices.
7. Water supplies with high conductivity (above 700
µΩ) must be precon-
ditioned for proper operation and longevity of the humidifier.
Water supply A 16- to 20-mesh strainer must be installed in the water supply to the water
and glycol units to prevent clogging of brazed plate condenser. This is a field
item.
N
OTE: Because of an ongoing program dedicated to product improvement,
specifications are subject to revisions without notice. APC assumes no
responsibility, and disclaims all liability for damages resulting from use of
this information or for any errors or omissions.