20 kVA - 80 kVA UPS
User’s and Installation Manual
1015543
Revision D
23
Figure 10. Five-wire installation of UPS units from 40 to 80 kVA with two-cable input.
Table 4. Fuse and cable dimensions for five-wire installations of UPS units from 40 to 80 kVA
using two cable input. Note that the fuse numbers and the cable letters refer to the numbers/
letters in figure 10. Slow gG/gL fuses should be used to protect cables.
*Please note that the battery cables are delivered with the external battery cabinets to
install the external battery cabinet next to the UPS. Cables with higher current capacity are
needed if the external battery cabinets or racks are installed with a distance from the UPS.