Hardwiring
Attention: Wiring must be performed by a qualified electrician.
1. Install a utility circuit breaker in accordance with local electrical codes (see tables below) for
input wiring only.
2. Switch the UPS input circuit breaker (see A) and utility circuit breakers OFF.
3. Remove the access panel (see B).
4. Remove circular knockouts.
5. Run wires through access panel to terminal blocks. Wire to ground block first. Adhere to all
national and local electrical codes. (See tables and graphics.)
6. Use appropriate glands to achieve strain-relief on the hardwired input and output power cables.
XLT, XLJ, AND XLTW MODELS
Input Connection Output Connection (optional)
Wire to L1, L2, and .
Wire to L1A, L2A, and
.
System Wiring Voltage Current
Full Load
(Nominal)
External Input
Circuit Breaker
(typical)
Wire Size
(typical)
SURT7500XLJ,
SURT7500XLT,
SURT7500XLTW
Input & Output 200/208/220V 40 amps
XLTW- 38 amps
50 amps / 2-pole for
Input Wiring Only
#8AWG/
10mm
2
SURT10000XLJ,
SURT10000XLT,
SURT10000XLTW
Input & Output 200/208/220V 54 amps
XLTW-50 amps
70 amps / 2-pole for
Input Wiring only
#6AWG/
16mm
2
XLI MODELS
Input Connections Output Connection (optional)
Single-Phase: Wire to L1, N, and .
Three-Phase: Wire to L1, L2, L3, N, and
.
Wire to L1A, N1, and
.
System Wiring Number
of
Phases
Voltage Current
Full Load
(Nominal)
External Input
Circuit Breaker
(typical)
Wire Size
(typical)
Input 1 220/230/240V 38 amps 50 amps / 2-pole 10mm
2
Input 3+
Neutral
380/400/415V 14 amps / phase when
online, 38 amps on L1
in bypass
50 amps / 4-pole 10mm
2
SURT7500XLI
Output 1 220/230/240V 38 amps (not required) 10mm
2
Input 1 220/230/240V 50 amps 63 amps / 2-pole 16mm
2
Input 3+
Neutral
380/400/415V 18 amps / phase when
online, 50 amps on L1
in bypass
63 amps / 4-pole 16mm
2
SURT10000XLI
Output 1 220/230/240V 50 amps (not required) 16mm
2
Page view 3