45Uniflair LE Accessories Manual
4. Press ENTER.
5. Select HARDWARE SETTINGS and press ENTER.
6. Navigate to “DIGITAL INPUT 4 CONFIGURATION”.
7. Check to ensure the existing setting is not used. If this does not correspond to your settings, whatever
function is currently attributed to that digital input of the control will be lost at the end of this procedure
and replaced with the one relative to the operation of the fire-smoke sensor.
8. Press ENTER until the cursor stops under NOT USED.
9. Press UP or DOWN until “SMOKE-FIRE SENSOR” appears on the display.
10.Press ENTER.
11. To exit, press the ESC key and navigate to the main screen.
After completion of the above procedure, an alarm signal displays on the display interface in case of fire or
smoke, and the unit stops operating.
Using the touchscreen
Path: Main > Configuration > Unit > Digital Inputs
1. Turn on the power to the unit and wait for the touchscreen to display.
2. Set the following configurations:
NOTE: Settings may appear on a different screen.
Digital Input 4 Configuration: Smoke-Fire Sensor
Digital Input 4 Function: Alarm Signaling
Digital Input 4 Normal State: Normally Open
3. Press the Home button to return to the main screen.
Page view 46