75Uniflair LE Accessories Manual
Ethernet LED Displays the status of the physical network connection (Ethernet connection signals), regardless
of whether the network parameters are correct. This LED flashes green when transmitting data.
Connecting to a PC
To connect the pCOWeb cable to a PC, connect the cable to the appropriate port.
Required equipment
Computer with a Web browser, for example Internet Explorer
, fitted with an Ethernet network interface.
pCOWeb card installed on the pCO controller
Network cable
Other requirements
Turn off the power to the pCO controller.
PC Configuration
NOTE: It is necessary to have administrator status for your PC to deactivate the Windows™ firewall.
The PC communicates with pCOWeb if settings on both devices are configured correctly.
The pCOWeb default settings can only be changed once the connection has been established with the PC.
When first accessing the device, the PC needs to be configured for adaption to the pCOWeb default settings.
Disable the firewall
The firewall must be disabled to access pCOWeb.
1. On the Windows-based PC, select Start at the bottom-left corner of the screen.
2. Select Control Panel. The Control Panel window displays.
3. Select Windows Firewall.The Windows Firewall window displays.
4. Select Off.
5. Select OK to apply the changes and close the window.
Setting the IP address and subnet mask
The PC does not use DHCP and uses the IP address of:
172.16.0.100
The Subnet mask field must also be set (the Gateway is not required).
1. On the Windows-based PC, select Start at the bottom-left corner of the screen.
2. Select Control Panel. The Control Panel window displays.
3. Select Network Connections. The Network Connections window displays.
4. Select Local Area Connection. The Local Area Connection Status window displays.
5. Select Properties. The Local Area Connection Properties window displays.
Red steady followed by
repeated green-red
During a firmware update, this shows
the writing of block B to non-volatile
memory.
Do not interrupt the power supply.
Condition Description
Green steady Correct Ethernet data connection signals
Green flashing Correct Ethernet data exchange
Red No Ethernet signal detected
Condition Description Notes