59Uniflair LE Accessories Manual
Configuration
Using the LED display
1. Turn on the power to the unit and wait for the main screen to appear on the display
2. Press Prg.
3. Select SERVICE MENU, then press ENTER.
4. Enter the password.
NOTE: The password is found inside the envelope attached to the manual. If the password has been
changed, enter the new password instead
5. Press ENTER.
6. Select HARDWARE SETTINGS, then press ENTER.
7. Navigate to DIGITAL INPUT 2 CONFIGURATION.
8. Check to ensure that the existing setting is not used. If this does not correspond to your settings,
whatever function is currently attributed to that digital input of the control will be lost at the end of this
procedure and replaced with the one relative to the operation of the flooding detector.
9. Press ENTER until the flashing cursor stops under NOT USED.
10.Navigate to FLOODING SENSOR appears on the display.
11. Press ENTER.
12.To exit, press the ESC key and navigate to the main screen.
13.Test the accessory to ensure proper function. The alarm will trip when a 24 V signal is received due to
water presence.
Additional Settings
1. Under Hardware Settings, select Flooding Alarm.
The Off setting on the alarm defaults to “N”. This indicates that the unit will not shutdown when the
alarm activates.
2. Change this setting to "Y" to enable an active leak/flooding/condensate alarm to shutdown the unit.
3. By default, “Valve Closed” on AI. is set to "N". Selecting "Y" enables the water valve (if applicable) to
close if the leak/flooding/condensate pump alarm is active.
Using the touchscreen
Path: Main > Configuration > Unit > Digital Inputs
1. Turn on the power to the unit and wait for the touchscreen to display.
2. Set the following configurations:
Digital Input 4 Configuration: Water Detection Sensors
Digital Input 4 Function: Alarm Signaling
Digital Input 4 Normal State: Normally Open
3. Press the Home button to return to the main screen.
Maximum Power Input 1.5 VA
Maximum length of
wiring from sensor to
SAS module
500 m (1640 ft), with single-wire cable and double
insulation
Length of tape sensor 25 m (82 ft)
Diameter of stainless
steel wiring for tape
sensor
0.6 mm (0.24 in.)
Power Details Description