If the card is placed in the last position of the supervision serial line, pins 2 and 3, you must connect a 120-1/4
W end line resistor.
Configuring using the LED display
NOTE: If installing multiple units on the network, each unit needs a unique address to avoid conflicts.
1. Press Prg on the display interface.
2. Select SETTINGS.
3. Enter the password.
4. Select SERIAL/MODEM SETTINGS.
5. Enter the following:
a. Serial Address
b. Serial Speed
c. Protocol: Modbus
6. Navigate to the main screen.
Configuring using the touchscreen
Path: Main > Configuration > Unit > Communication
1. Turn on the power to the unit and wait for the touchscreen to display.
NOTE: Settings may appear on a different screen.
2. Enter your credentials and begin configuration.
BMS1 Serial Address: Enter the required Serial Address
BMS1 Serial Speed: Enter the required Serial Speed.
BMS1 Serial Protocol: Modbus
Remote ON/OFF Only Through Serial Communication: Enable
3. Press the Home button to return to the main screen.
na4769a