65Uniflair LE Accessories Manual
NOTE: Ensure that the wall-mounted sensor is installed away from direct airflow to ensure proper
pressurization detection.
tLAN connection
1. Using a screwdriver, remove the analog selection cover on the controller inside the unit.
2. Using cutting nippers, remove the precut plastic hatch to access the tLAN card slot.
3. Aligning the connector pins, insert the tLAN card into the slot and push into place, making sure the card
is pushed against the two plastic supports on the case.
4. Put the cover back on the controller and snap into place.
Supply power connections
1. Route the tLAN cables and supply power harness to the electrical panel.
2. Connect J3 from the AFPS to the green connector on the tLAN card.
NOTICE
UNPROTECTED OUTPUTS
Be sure all pins on the circuit board are properly seated and not bent or touching other
pins.
Failure to follow these instructions can result in equipment damage.