APC ACFS76080 Installation Manual Page 88

  • Download
  • Add to my manuals
  • Print
  • Page
    / 100
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 87
Uniflair LE Accessories Manual86
NOTE: Settings may appear on a different screen.
2. Enter your credentials and begin configuration.
BMS1 Serial Address: Enter the required address
BMS1 Serial Speed: Enter the required serial speed
BMS1 Serial Protocol: Modbus
Remote ON/OFF Only Through Serial Communication: Enable
3. Press the Home button to return to the main screen.
Status LED
The Status LED (left) indicates the status of communication with the controller and the status of the pCOnet
controller.
Starting sequences, power-up, and restarting
The starting sequence on power-up or after restarting pCOnet controller provides the following sequence:
1. Off for two seconds.
2. Two seconds after restarting:
quick flash > red > green > red > green
3. Five seconds after restarting:
steady green
Approximately 50 seconds after restarting, communication begins. The following table provides active alarm
conditions and descriptions on the status LED.
Once the starting sequence has been completed, the Status LED flashes to indicate the quality of
communication with the pCO controller.
RS485 LED
The RS485 LED is located on the right side of the card, and indicates the status of communication with the
BACnet MS/TP network (RS485) and displays the following information:
For starting sequence on power-up or after rebooting the pCOnet, the RS485 LED switches in the following
sequence:
1. Off for approximately 50 seconds.
2. Approximately 50 seconds after restarting the pCOnet controller, a slow green–red–green–red light
displays and the BACnet MS/TP network activates.
Status of communication with the BACnet MS/TP network
Once the starting sequence completes, the RS485 LED flashes to indicate the quality of communication with
the BACnet MS/TP network. The following table provides active alarms conditions and descriptions on the
status LED.
Condition Description
Quick green > OFF > green Indicates communication with the pCO controller is normal.
Slow red > OFF >r ed Indicates communication has not been established with the pCO controller.
Green > red > green Indicates that the pCOnet has detected an error, or that there is a temporary
lack of response from the pCO controller.
Condition
Description
Green with occasional red flashes Communication is OK (BACnet MS/TP meaning: green
ON = pCOnet keeps the Token (control of the MS/TP
network); green OFF = pCOnet DOES NOT keep the
Token; red on = Poll-For-Master, search for a Master to
pass the Token to).
Page view 87
1 2 ... 83 84 85 86 87 88 89 90 91 92 93 ... 99 100

Comments to this Manuals