EcoBreeze System Operation and Maintenance30
Module Configuration
The Module configuration settings define which components are available and how the Module
should operate. Up to eight Modules can be housed in a common Frame. The Modules are fully
self contained with the exception of the common Frame-based water system to support the
indirect evaporative cooling. Each Module has its own controller. The controllers in the Modules
are coordinated by the Frame active master controller.
View Module status
Path: Main > View Module Status > Measurements > Select Module (N) > Module (N) Sensors
These sensor readings cannot be changed on this screen: it is view only. No password is
required to view Module Status. Module status is divided into two menus:
Fans & air
Supply Air: °F/°C - The temperature of the conditioned air.
Supply Humidity: %R.H. - The relative humidity of the conditioned air.
Return Air: °F/°C - The temperature of the air to be conditioned.
Return Humidity: %R.H. - The relative humidity of the air to be conditioned.
IT Air Flow: CFM / L/s - The volume of IT air supplied by the Module.
IT Fan Power: W - The rate of energy consumed by the Module IT fans.
OA Fan Speed: rpm - The rotational speed of the OA fan.
OA Fan Power: W - The rate of energy consumed by the Module OA fan.
IEC Air: °F/°C - The temperature of the indirect evaporative cooled air.
Filter DP: Pa - The differential pressure across the air filter.
CAUTION
AUTHORIZED PERSONNEL ONLY
Procedures in this section must be performed by Schneider Electric authorized personnel.
The settings are defined at the factory. Changing the settings incorrectly can cause
serious malfunctions and damage to your system. Only qualified service personnel should
make changes to these settings.
Failure to follow these instructions can result in injury or equipment damage.