APC ACECFR20200SE4 Installation Manual

Browse online or download Installation Manual for Hardware cooling accessories APC ACECFR20200SE4. APC ACECFR40101SE3 hardware cooling accessory User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 60
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
Operation and Maintenance
Cooling Solutions
EcoBreeze™ System
ACEC101SE, ACEC200SE, ACEC201SE,
ACECFR20101SE, ACECFR20200SE,
ACECFR20201SE, ACECFR40101SE,
ACECFR40200SE, ACECFR40201SE
990-3999D-001
Publication Date: June 2014
SUPPLY
BLOWE
R
ACCE
SS
COIL
ACCESS
SUPPL
Y
BLOWE
R
ACCESS
COIL
ACCESS
SUPPLY
BLOWER
ACCESS
COIL
ACCESS
SUPPL
Y
BLOWE
R
ACCESS
COIL
ACCESS
Page view 0
1 2 3 4 5 6 ... 59 60

Summary of Contents

Page 1

Operation and MaintenanceCooling SolutionsEcoBreeze™ SystemACEC101SE, ACEC200SE, ACEC201SE, ACECFR20101SE, ACECFR20200SE, ACECFR20201SE, ACECFR40101SE

Page 2

EcoBreeze System Operation and Maintenance4Air-to-air heat exchangeThe Module outdoor fan is used to move the ambient air, used as the cooling medium,

Page 3 - Contents

5EcoBreeze System Operation and MaintenanceBasic system operation using HACS and a raised floor• Hot air from the servers is controlled through Hot A

Page 4

EcoBreeze System Operation and Maintenance6ConfigurationModulesThe EcoBreeze is comprised of up to eight identical Modules contained in a common Frame

Page 5

7EcoBreeze System Operation and MaintenanceCommissioningDANGERHAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASHTurn off all power supplying this equip

Page 6

EcoBreeze System Operation and Maintenance8Inspection ChecklistsInitial inspection The initial inspection ensures that the equipment has been properly

Page 7 - Important Safety Information

9EcoBreeze System Operation and MaintenanceElectrical inspection checklistThe electrical inspection verifies that all electrical connections are secur

Page 8 - General Information

EcoBreeze System Operation and Maintenance10Mechanical inspectionThe mechanical inspection verifies that all mechanical components and connections are

Page 9 - Features

11EcoBreeze System Operation and MaintenanceUser interface inspection checklistThe user interface inspection verifies that the sensors and internal co

Page 10 - Proportional DX cooling

EcoBreeze System Operation and Maintenance12OperationControllersController redundancyThe Frame system uses dual master controllers: a main Module and

Page 11 - Door safety interlock

13EcoBreeze System Operation and MaintenanceUsing the Display InterfaceThere are two primary user interfaces: a graphical user interface (GUI) and the

Page 12 - Configuration

Schneider Electric IT Corporation Legal DisclaimerThe information presented in this manual is not warranted by the Schneider Electric IT Corporation t

Page 13 - Commissioning

EcoBreeze System Operation and Maintenance14Menu screensOn any status screen press the > or < arrow to open the top level menu screen. If the di

Page 14 - Inspection Checklists

15EcoBreeze System Operation and MaintenanceNavigating sub menus You select the main menu item by pressing the ENTER key. The screen that opens is a s

Page 15 - Ensure that the:

EcoBreeze System Operation and Maintenance16Start the SystemPath: Main > Operate > On/OffTo start the System from the scrolling status screen, p

Page 16 - Mechanical inspection

17EcoBreeze System Operation and MaintenanceAbout EcoBreezePath: Main > About EcoBreezeThis is a “view only” screen. No password is required. The s

Page 17 - Final inspection

EcoBreeze System Operation and Maintenance18The Embedded Display Menus Some settings are only available by accessing the embedded display for the inte

Page 18 - Operation

19EcoBreeze System Operation and MaintenanceMain menuPress >> at the top of the far right column (Address Status Mode) of the screen to display

Page 19 - Using the Display Interface

EcoBreeze System Operation and Maintenance20Configure the FrameThe Frame distributes power from the mains to the Modules and its master controllers co

Page 20 - Menu screens

21EcoBreeze System Operation and MaintenanceActive Flow Controller (AFC) status will be visible inside a highlighted box when the screen opens. Press

Page 21 - Passwords

EcoBreeze System Operation and Maintenance22Run Hours:• Pump A: - 0 Hrs• Pump B: - 0 Hrs• Water Treatment: - 0 Hrs• Module 1 Compressor• Module 2

Page 22 - Set identification

23EcoBreeze System Operation and MaintenanceReset (Option) Run HoursEnter Yes to confirm ESC to exitYes/NoNo will be in the highlighted box on the scr

Page 23 - About EcoBreeze

ContentsEcoBreeze System Operation and Maintenance iSafety...

Page 24 - The Embedded Display Menus

EcoBreeze System Operation and Maintenance24Water Controls. (Requires device password)• Lead Pump: A or B• Pri Water Src: A or B• Drain Basin: Basi

Page 25 - Main menu

25EcoBreeze System Operation and Maintenance• DP Sensor Sel: – None: No differential pressure (DP) measurements are to be supplied to the unit.– 4-20

Page 26 - Configure the Frame

EcoBreeze System Operation and Maintenance26Water Service. (Requires admin password)• Setpoint: 500 - 15000 uS/cm• Deadband: 25 - 15000 uS/cm• Cond

Page 27 - ENTER to open the AFC screen

27EcoBreeze System Operation and MaintenanceActiveFlowCtrl Setup. Configure AFC settings.• Edit Config– Enable/Disable (set to Enable before changing

Page 28 - OWN arrow. Press ENTER

EcoBreeze System Operation and Maintenance28View Setup. Press the UP or DOWN keys to view all sensor information being collected by the Frame controll

Page 29

29EcoBreeze System Operation and MaintenanceBuilding management system (BMS)The Modbus interface allows the EcoBreeze to communicate with a BMS. The M

Page 30

EcoBreeze System Operation and Maintenance30Module ConfigurationThe Module configuration settings define which components are available and how the Mo

Page 31 - OWN key to

31EcoBreeze System Operation and MaintenanceDX components• Discharge Pres.: psi/kPa - The pressure at the discharge port of the compressor.• Dischar

Page 32 - P or DOWN

EcoBreeze System Operation and Maintenance32View Setup. This is a read-only view of the above configurations. No password is required. • Module # - A

Page 33

33EcoBreeze System Operation and MaintenanceEnvironment ControlThe EcoBreeze can sense ambient temperature and automatically switch between DRY and WE

Page 34

EcoBreeze System Operation and MaintenanceiiOperation... 12Controller

Page 35

EcoBreeze System Operation and Maintenance34The setpoint for each mode must be within the following ranges:• Supply Air - 75.0°F (See “Air Controls”

Page 36 - Module Configuration

35EcoBreeze System Operation and MaintenanceEvent LogThe event log saves status information and a message each time a change in the system is detected

Page 37 - Configure Modules

EcoBreeze System Operation and Maintenance36Respond to AlarmsWhen an alarm is triggered, the display alerts you through the following methods:• The s

Page 38

37EcoBreeze System Operation and MaintenanceAFC ModBus Communication ErrorCritical • Check ModBus cable between AFC master sensor and EcoBreeze frame

Page 39 - Environment Control

EcoBreeze System Operation and Maintenance38Primary Water Supply Loss Critical • Check the wiring, verify city water pressure is adequate (if applicab

Page 40

39EcoBreeze System Operation and MaintenanceAmbient Temperature Sensor Fault, RIM (Frame redundant controller)Critical • Check the wiring. • Check and

Page 41 - NTER to Confirm

EcoBreeze System Operation and Maintenance40Module alarms• “COMPRESSOR ALARMS” on page 40• “ELECTRONIC EXPANSION VALVE (EEV) ALARMS” on page 40• “F

Page 42 - Path: Main > Clear Alarms

41EcoBreeze System Operation and MaintenanceEEV Temperature Sensor Fault Critical • Check the suction pressure transducer reading. • Check the suction

Page 43

EcoBreeze System Operation and Maintenance42Discharge Temperature Sensor Fault Warning • Check the wiring. • Check and clean the sensor.• Check the se

Page 44

43EcoBreeze System Operation and MaintenanceSupply Temperature Sensor FaultCritical • Check the wiring. • Check and clean the sensor.• Check the senso

Page 45

EcoBreeze System Operation and Maintenance iiiRespond to Alarms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

Page 46 - Module alarms

EcoBreeze System Operation and Maintenance44TroubleshootingNOTE: The EcoBreeze operates using controllers to control internal functions along with var

Page 47

45EcoBreeze System Operation and MaintenanceModule powered but will not operate• System is off• Remote shutdown or input contact is active• System is

Page 48

MaintenanceGeneral Task DescriptionsFans • Verify that the fan hardware is tight.• Verify that electrical connection is secure.FiltersClean/replace

Page 49

47EcoBreeze System Operation and MaintenanceInspecting the Heat Exchangers. Inspect heat exchangers Module by Module. Remove power from the Module to

Page 50 - Troubleshooting

General cleaningInspect and clean the EcoBreeze system on a regular basis. Do not use cleaners, chemicals, or other materials with strong fumes or odo

Page 51

49EcoBreeze System Operation and MaintenanceMonthly Preventive MaintenancePrepared By: _________________________________Model Number: ________________

Page 52 - Winter protection

EcoBreeze System Operation and Maintenance50Quarterly Preventive Maintenance* Perform all the Monthly Preventive Maintenance items and the items below

Page 53 - Electrical

51EcoBreeze System Operation and MaintenanceSemi-Annual Preventive Maintenance* Perform all the Monthly and Quarterly Preventive Maintenance items and

Page 57 - Annual Preventive Maintenance

Worldwide Customer SupportCustomer support is available at no charge via e-mail or telephone. Contact information is available at www.apc.com/support/

Page 58

1EcoBreeze System Operation and MaintenanceSafetyImportant Safety InformationRead the instructions carefully to become familiar with the equipment bef

Page 59

EcoBreeze System Operation and Maintenance2General InformationOverviewThe EcoBreeze™ is a modular indirect evaporative and air-to-air heat exchanger c

Page 60 - Worldwide Customer Support

3EcoBreeze System Operation and MaintenanceModule(s)Modules are fully self-contained cooling apparatus, with the exception of common Frame based water