14 APC Redundant Switch: Installation and Operation Manual
Configuration
b. Restart the computer on which PowerChute
plus
is
installed.
c. Start PowerChute
plus
. Communication is to
UPS
-
A
.
d. Configure
UPS
-
A
according to your requirements.
e. Set the
UPSID
to
UPS
_
A
.
When one
UPS
becomes
unavailable
When one of the two
UPS
s becomes unavailable to supply
AC
power, PowerChute
plus
sends the message “Self test failed:
invalid test.” Any of the following conditions will cause the
message to occur:
•A
UPS
self-test fails.
Communication with the alternate
UPS
is lost.
The voltage of the alternate
UPS
is out of range.
UPS
-
A
fails, and the Redundant Switch transfers the
power input and PowerChute
plus
communication to
UPS
-
B
.
To regain high availability for your system, correct the problem
as soon as possible. See “Troubleshooting” on pa ge18.
Note
When any self-test of the primary
UPS
occurs,
the Redundant Switch switches power and
communication to the other
UPS
, causes a self-
test of that
UPS
, and then switches back. This is
normal behavior.