MX06 Power Plant User’s Manual Page 14
RELAY
OUTPUT
J2 CONNECTOR
DESIGNATIONS
OUTPUT RELAY NOTES
NC 1
MAJOR C 2
NO 3
NC 4
MINOR C 5
NO 6
NC 7
VERY LOW V C 8
NO 9
Figure 3.8-1 Output Relay Connections
External Alarm Input Connections
Four user-defined alarm inputs are provided on connector J3. Each alarm input can be
individually programmed for alarm priority (MAJOR or MINOR) and input contact configuration
(Normally Open or Normally Closed). Each alarm input utilizes a two wire connection, with one
side of the contact attached to user input pin and the other side connected to one of the –BAT
pins. The input alarm contacts must be isolated (“dry”).
The factory default settings for these alarms are MAJOR alarm priority and a Normally Open
(NO) contact input, closed for alarm. Changing the contact input to Normally Closed or
programming an alarm condition for MINOR requires a change to dipswitch S1 mounted on the
system Controller Board. See application details in Section 5.
A cable (0W09051) is available to connect the input alarms. Refer to Figure 3.7-2 for rear
panel connections.
EXTERNAL ALARM
INPUT
J3 CONNECTOR
DESIGNATIONS
USER ALARM NOTES
#1 1
#2 2
#3 4
#4 5
#1 C 6
#2 C 7
#3 C 9
#4 C 10
Figure 3.8-2 External User Input Connections