MX06 Power Plant User’s Manual Page 23
MX06-50 Rectifier Configuration
The system Controller Board must know if a rectifier is present for each of the five slots. This is
done by the properly setting the dipswitch S2 (“RECT PRESENT”) on the Controller Board. If a
rectifier is not
present in a given slot, the corresponding switch position must be set to the “ON”
condition. The ON direction is labeled on the body of the dipswitch. Figure 5.3-1 locates switch
S2 on the PC board.
Figure 14 shows one style of dipswitch that may be on the board. On some controller boards,
dipswitch S2 may consist of 10 small switches (instead of 5 large switches). In that case the
switches must be used in pairs. I.E., for rectifier 1, the top 2 are a pair, for rectifier 5, the bottom
2 are a pair, and likewise for the middle switches.
MX06-50 Programmable Alarms
The GMT alarm, battery circuit breaker alarm and the AC / Input Healthy alarm can each be
programmed to either MAJOR or MINOR alarm priority. A three-pin jumper header is used for
each alarm in the manner shown in Figure 5.3-2. Figure 5.3-1 locates the jumpers on the PC
board. If no jumper is in place, then no alarm will be reported.
Figure 5.3-2 MX06-50 Jumper Programming.
Alarm
Jumper
Designator
Major
Setting
Minor
Setting
No Alarm
Output
Factory
Setting
GMT
Alarm
J5
Pins
2 and 3
Pins
1 and 2
No
Jumper
Major
Battery
Breaker
Alarm
J3
Pins
2 and 3
Pins
1 and 2
No
Jumper
Major
AC / Input
Healthy
J2
Pins 2
and 3
Pins
1 and 2
No
Jumper
No Alarm
Figure 5.3-3 MX06-50 Alarm Jumpers
MAJOR
1 2 3
MINOR
1 2 3