APC NBRK0320E Datasheet Page 102

  • Download
  • Add to my manuals
  • Print
  • Page
    / 210
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 101
Advanced View: Configuring Pods and Alerts
Using Your Appliance 93
Edit.
2. The Edit Periodic E-mail Report window opens. This window contains the following fields:
3. Type the appropriate values in the fields.
4. Specify Advanced Scheduling for the Periodic Report (optional). By default, all Periodic Reports
will be generated according to the Interval value you specify. However, you can specify that a
Periodic Report will be active only occur during specific time ranges. To configure Advanced
Scheduling:
a. Click Advanced Scheduling.... The Advanced Scheduling window opens.
b. By default, all time periods in the schedule are set to Enabled. To disable the Periodic Report for
a currently enabled period of time, highlight the period of time by clicking-and-dragging over the
desired time range, and then click Disable. To enable the Periodic Report for a currently disabled
period of time, highlight the period of time by clicking-and-dragging over the desired time range,
and then click Enable.
Field Description
Enabled Check this check box to enable periodic e-mail reporting.
Include camera pictures Check this check box to include current image captures by
Camera Pod 120s connected to the appliance in the e-mailed
report.
Include Maps Check this check box to include any maps that are stored on the
appliance in the e-mailed report.
Include Graphs Check this check box to include graphs of the sensor readings
for all sensors that are associated with the appliance in the e-
mailed report.
Interval The frequency with which e-mail reports will be generated.
Sensor Priority Acts as a filter that can be used to limit the amount of sensor
data that is included with the periodic report. You can select
High, Medium, or Low priority settings:
High: Only sensor data associated with physical sensors that
are integrated with or connected to the appliance are included
in the report. Sensor data associated with remote devices,
such as MIB II data gathered from remote targets using Basic
Device Crawlers and Advanced Data that is gathered using
add-on applications such as Advanced Device Crawlers, is not
included in the report.
Medium: Sensor data associated with physical sensors and
with Advanced Data sensor sets from remote devices (such as
that which is gathered using Advanced Device Crawlers) is
included in the report. Data associated with remote devices
that is not grouped in an Advanced Data sensor set, such as
MIB II data gathered from remote targets using Basic Device
Crawlers, is not included in the report.
Low: Sensor data from all sensors is included in the report.
E-mail Addresses The addresses to which periodic e-mail reports will be
delivered.
Page view 101
1 2 ... 97 98 99 100 101 102 103 104 105 106 107 ... 209 210