Advanced View: Defining Thresholds
Using Your Appliance 147
Above Value for Time Threshold
An above value for time threshold is defined by specifying a maximum acceptable value for the sensor
and a maximum period of time value. If the value reported by the sensor exceeds the specified value for
more than the specified period of time an alert condition is reported. To define an above value for time
threshold:
1. Start the Camera Pods, Sensor Pods, or Device Crawlers task by double-clicking on the appropriate
icon.
2. Click Sensors... to open the Sensor Configuration window.
3. Select from the Sensors selection list the sensor for which you will define a threshold. A list of
thresholds that have been previously defined for the selected sensor, if any, appears in the
Thresholds selection list.
4. Click Add... to open the Select Threshold window. Select Above Value for Time Threshold and
then click OK to close the Select Threshold window.
5. Type in the Threshold Name field a name for this threshold.
6. Specify Basic threshold settings. From the Basic tab in the Thresholds pane:
a. Type in the Maximum field (or use the arrows in the field to specify) the highest acceptable
value for the selected sensor. This is the value that, if exceeded for greater than the number of
seconds specified in the Time Allowed Above Maximum field, will result in an alert condition.
b. Type in the Time Allowed Above Maximum field (or use the arrows in the field to specify) the
number of seconds that the reported value can exceed the value specified in the Maximum field
before an alert condition is generated.
c. Check the Enabled check box to enable the threshold. If this check box is not checked, the alert
threshold will be saved but will not be active.
d. Add to the Threshold-Specific Addresses list the e-mail addresses of any personnel to whom e-
mail alert notifications should be sent if this threshold triggers an alert condition. Click Add...,
type in the e-mail address to which the alert notification will be sent, and then click OK.
If you’ve installed an SMS-capable modem you can deliver alert notification to SMS-enabled
devices by entering threshold-specific addresses for them in the following format:
sms:sms_device_address
where sms_device_address is the telephone number or e-mail address associated with the SMS-
enabled device (for example, “sms:5123334444” or “sms:[email protected]”).
7. If desired, specify Advanced Threshold settings. All Advanced threshold settings are optional. From
the Advanced tab in the Thresholds pane:
Specify a Return To Normal Delay value. Use the controls to specify the number of seconds
that must pass after this threshold has returned to normal before the threshold state is considered
Note
These threshold-specific notifications are sent only if your appliance has one or
more Alert Actions defined that use the Send E-Mail Message alert notification
method and that have the Include Addresses from Thresholds check box
checked. For more information, see “Alert Actions” on page 59 and “Advanced
View: Creating Alert Actions” on page 161.