APC INROOM ACPSC3000 Operations Instructions Page 25

  • Download
  • Add to my manuals
  • Print
  • Page
    / 80
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 24
InRoom CW/DX – Operating Instructions 25
4.2 Technical Data - P A/G/ACW/GCW 211/311 D - 1-circuit
1
For electrical data, heating and humidifi er equipment see page 31-32
2
For A/ACW units for all sizes, the refrigerant charge is 1.0 kg (2.2 lb)
3
For dimensions and weights, see page 30
Modell 211 311
460V - 60 Hz 460V - 60 Hz
DX-Kälteleistung total
75°F(24°C)/50% r.F.
sensibel
MBH
(kW)
MBH
(kW)
21.4
(73.0)
21.4
(73.0)
32.8
(112.0)
30.7
(104.8)
Verhältnis sens./total
1 0.94
Komp.-Leistungsaufnahme
kW
4.4 6.8
EER
max
(ASD...A/G)
kW/kW
((BTU/h)/W)
3.89
(13.28)
4.00
(13.56)
CW-Kälteleistung total
24°C(75°F)/50% r.F. sensibel
kW (MBH)
23.9 (80.0)
21.7 (73.2)
34.0 (113.7)
30.8 (103.7)
Verhältnis sens./total
0.91 0.91
Kompressortyp
1
C3 C13
Füllmenge G, GCW
2
lb (kg)
2.8 (6.2) 3.9 (8.6)
Wasservolumenstrom G
gpm (m³/h)
2.5 (11.0) 3.6 (15.8)
dp wasserseitig G
ft (kPa)
30 (
10.0)
31 (
10.4)
Wasservolumenstrom CW
gpm (m³/h)
4.1 (17.8) 5.9 (25.3)
dp wasserseitig CW
ft (kPa)
44 (14) 29 (9.3)
CW-Registerinhalt
gal (dm³)
9.6 (2.54) 14.3 (3.78)
CW - Ventilgröße (3-Wege)
1 1 1/4
Luftvolumenstrom
cfm (m³/h)
6500 (3826) 9000 (5300)
Ventilatoranzahl
1 1
Max. ext. stat. Druck
A / G
in.wg (Pa)
450 (1.81) 450 (1.81)
Schalldruckpegel
dBA
51.8 56.5
Vent.-Leistungsaufnahme
hp (kW)
1.1 (1.5) 1.4 (1.9)
Max. ext. stat. Druck
ACW/GCW
in.wg (Pa)
450 (1.81) 420 (1.69)
Schalldruckpegel
dBA
53.1 56.8
Vent.-Leistungsaufnahme
hp (kW)
1.3 (1.7) 1.6 (2.1)
Baugröße
3
1 2
Type
DX-cooling capacity total
24°C(75°F)/50% r.h.
sensible
kW
(MBH)
kW
(MBH)
Ratio sensible/total
Compressor power consumption
kW
EER
max
(ASD...A/G)
kW/kW
((BTU/h)/W)
CW-cooling capacity total
24°C(75°F)/50% r.h. sensible
kW (MBH)
Ratio sensible/total
Compressor type
1
Refrigerant charge G, GCW
2
kg (lb)
Water fl ow G
m³/h (gpm)
dp water side G
kPa (ft)
Water fl ow CW
m³/h (gpm)
dp water side CW
kPa (ft)
CW coil content
dm³ (gal)
CW - valve size (3-way)
inch
Airfl ow
m³/h (cfm)
Number of fans
Maximum external static pressure
A / G
Pa (in.wg)
Sound pressure level
dBA
Fan power consumption
kW (hp)
Maximum external static pressure
ACW/GCW
Pa (in.wg)
Sound pressure level
dBA
Fan power consumption
kW (hp)
Cabinet size
3
Page view 24
1 2 ... 20 21 22 23 24 25 26 27 28 29 30 ... 79 80