InRoom CW/DX – Operating Instructions 61
9.1.6 Maintenance
Electrical Hazard:
1. Switch the cooling off unit at the Controller.
2. Tur n the main disconnect switch to the OFF position.
3. Check for voltage.
4. Begin work if no voltage is present.
The following work and checks can be carried out:
- Check steam hoses, condensate hoses, water hoses and other parts of the humidifi er for external effects
or wear.
- Flush out the water drain.
Replacing the steam cylinder
The steam cylinder needs replacing if the electrodes are so highly insulated due to the increasing calcifi cation
or furring that the water level in the steam cylinder constantly touches the sensor electrode.
The specially constructed water fi lling beaker provides additional safety. Excessive water is routed to an
overfl ow and then drained away from the unit.
Warning:
The temperature of the discharged water is approximately 60°C (140°F) during normal ope-
ration but can reach 100°C (210°F) briefl y, if the steam cylinder is emptied manually during
maintenance work.
The steam cylinder should be allowed to cool down slightly before removal.
The steam cylinder uses the alarm code 11x long on the humidifi er‘s printed circuit board in the electrical
section of the cooling unit. See Alarm table 2 on page 64 for details. If the alarm code 11x long occurs
repeatedly, the steam cylinder has worn out and must be replaced. The life of a steam cylinder depends on
the operating period and the hardness of the water.
Manual drainage
By means of a switch on the humidifi er
board, you can manually drain the
cylinder.
Put the switch into position "DR" to drain
the humidifi er.
After the drainage, the switch must be
reset to position "ON", or no humidifi -
cation can take place.
Position "ON" Position "DR"
Electrical Hazard:
Switch off the power supply circuits to the humidifi er before continuing the work.
Disconnect the electrical plug on the cylinder.
Release the hose clamp. Pull off the steam hose.
Unscrew the steam cylinder from the mount.
The new steam cylinder is installed in the reverse sequence. The humidifi er is re-started in accordance with
the recommendations of the chapter "9.1.4 Commissioning", which begins on page 56.