InRoom CW/DX – Operating Instructions
1.50
1.45
1.40
1.35
1.30
1.25
1.20
1.15
1.10
1.05
50%
40%
30%
20%
10%
-10 -8 -6 -4 -2 0 2 4 6 8 °C
14 17.6 21.2 24.8 28.4 32 35.6 39.2 42.8 46.4 °F
43
External water circuit
To seal the water circuit you must connect the unit to a chilled water ring mains, which contains for the ge-
neration of cold water either a chiller or a dry cooler or cooling tower. If the water quality is insuffi cient, we
recommend the additional installation of a 1000 micron strainer.
For protection against corrosion, use the anti-freezing solution if the water temperature passes under 5°C
or if the outside temperature is less than 0°C. All water lines need to be properly fl ushed prior to starting of
the equipment.
Add the following quantities of ethylenglycol (indicated as percentage of weight of the water quantity):
water or outside air temperature ethylenglycol
from 41 to 23°F (+5 to -5°C) 10%
from 23 to 14°F (-5 to -10°C) 20%
from 14 to 5°F (-10 to -15°C) 28%
from 5 to -4°F (-15 to -20°C) 35%
from -4 to -13°F (-20 to -25°C) 40%
average cooling water temperature
Correction coeffi cient for the pressure
drop in the water circuit when using
ethylenglycol
6.3.3 InRoom Water and Glycol Piping