9.1.5 Operation
The steam humidifi er is controlled and monitored by the controller. No further operating measures are
required for continuous operation.
Vary the humidifi er output by operating the DIP-switches A3/4 located on the humidifi er printed circuit
board.
The humidifi er operation is indicated by a green LED.
From the yellow LED you can see the state of operati-
on of the humidifi er (see diagrams 1, 2). The red LED
indicates if an alarm is active (see alarm table).
Yo u can also manually drain the steam cylinder (see
9.1.6 Maintenance on page 61). The position of the
TA RATE-switches 1-4 and the DIP-switches A2 and
B2 are not to be changed under any circumstances.
For this reason the switches are sealed.
100 % humidifi cation capacity
75 % humidifi cation capacity
50 % humidifi cation capacity
20 % humidifi cation capacity
DIP A2: Alarm relay status
Relay energized (contact closed)
when at least 1 alarm is active, other-
wise not energized (contact open).
Relay not energized (contact open)
when at least 1 alarm is active, other-
wise energized (contact closed).
Power supply 24 VAC
G/G0
manual
drainage
drain valve
fi l l valve
high level/foam
sensor
conductivity sensor
external TA M
immersed electrodes
maximal 5A
alarm relay
humidity sensor
external controller
remote ON/OFF
green LED
yellow LED
red LED
fi g . 1
3 days
2 days
3 days
7 days
DIP A5-6: Adjustment of the inactivity period, after
which the cylinder is completely drained
.
Page view 56