InRoom CW/DX – Operating Instructions
minimal 5°
56
Water drain
The drain is a plastic hose and is routed out of the unit by means through the openings in the unit provided
for this purpose (see graphic below).
When creating the drain, attention is to be paid to provision for cleaning. As the water drain is depressuri-
zed, route the drain hose directly into an open collector funnel to ensure free discharge. The drainage pipe
should be routed to the drain with suffi cient gradient (1/4 inch of a drop every 10 feet) and should be located
approximately 30 cm (11.81 inch) below the humidifi er. Attention is to be paid to temperature resistance
when plastic pipes are used. If copper pipe is used, it must be earthed. For the drainage pipe an inside
diameter of 32 mm (1 1/4 inch) is recommended. However, the minimum inside diameter should not be less
than 25 mm (1 inch).
9.1.4 Commissioning
Completely open the shutoff valve in the water supply line. As soon as the controller requires the humidifi er
function, the heating current is switched on; after approximately 30 seconds water is fed into the steam
cylinder through the inlet valve which opens, and fully automatic operation begins.
IMPORTANT NOTICE:
After the water pipes have been connected, the supply piping must be fl ushed for approx. 30 minutes,
where the water is directly conducted into the drain, without letting it fl ow into the steam humidifi er.
This removes residues or substances of the installation process, which otherwise could block the
fi l l valve and cause foam during the boiling process.
Decommissioning the humidifi er
The steam cylinder is to be emptied if the humidifi er has been out of operation for a long period (e.g. in
summer, decommissioning the air conditioning system etc.) (see 9.1.6 Maintenance - Drainage).
Supply
Drain
fi l ter shutoff valve
3.11 in
10.43 in
2.95 in
2.95 in