Single System
Start-up of the UPS System with the Wizard Enabled
Note: The default value of the wizard is ENABLE which is a prerequisite for carrying out
this procedure. See “Setting the Wizard“.
Note: Upon initial start-up, the UPS will autom atically guide you via the w izard to select
diff erent settings: language, current voltage, current frequency, and mode. If a wizard
prompt is ignored the default setting of the prompt will be enabled. You must complete the
wizard one time before you can disable it for subsequent start-up sessions of the UPS system.
Note: You must have your password ready as you will be asked to enter it during this
procedure. If you are in doubt about how to enter or set your password, see “Entering
the Password“and “Setting the Password“.
Note: When a settings value has been entered and confirmed by the prompt Done!,the
wizard automatically moves to the next display prompt after three seconds.
1. Power on the UPS system by turning the mains
input breaker (QM1) to the ON (closed)
position.
Note: If the prompt System init
error! Error code: 1-x appears on
the display screen, see “Error codes
for UPS system initialization under
“Status and Alarm Messages“.
System initialization..
2. When the Change language? (Y=Enter,
N=Esc) prompt appears on the display screen,
do one of the following:
A. Press ENTER to view the list of
languages, select one of the 18 languages
by using the UP/ DOWN navigation keys
and press ENTER againtoconrm.
B. Press ESC to move on to Change voltage
of 2XXV? (Y=Enter, N=Esc).
Change language?
(Y=Enter, N=Esc)
ENGLISH
Done!
Note: If the output breaker (QOP) is
ON (closed) at this point, yo
umust
Close QM1 to continue setting!
followed by ENTER ,andOpen
QOP to continue setting! followed
by ENTER.
Note: If the output breaker (QOP) is
ON (closed) the menu freezes and is
unable to continue.
Close QM1
to continue setting!
Open QOP
to continue setting!
990-3619B-001
MGE™ Galaxy™ 300 and MGE™ Galaxy™ 300i Operation
7