Note:
The screen displays the following characters:
- A indicates a fault appearance (or other data types)
2009/12/31 23:59:59 A
PFC fuse blown
- D indicates a fault disappearance
2009/12/31 23:59:59 D
PFC fuse blown
1. From the Default screen, press ENTER.
2. Go to EVENT LOG by using the UP/DOWN navigation keys and press ENT ER.
EVENT LOG
3. The screen displays the latest log event or the prompt No event.
4. Use the UP/DOWN navigation keys to go through the latest events.
5. Press ESC until you return to the Default screen.
Activate Controls
Note: W hen the comm and values INVERTER OFF or FORCE LOAD TRANSFER TO
BYPASS are activated, the Risk of load drop, continue or not? prompt appears. Press
ENTER to continue (or ESC to return to previous screens).
1. From the Default screen, press ENTER.
2. Go to CONTROLS by using the UP/DOWN navigation keys and press ENTER.
3. Go to one of the commands in the below table by using the UP/DOWN navigation keys.
4. Press ENTER to activate a command.
Note: When one of the command values from the below table has been activated, the prompt
Processing...... will be displayed for three seconds followed by the prompt Command is
accepted! if the command runs successf ully, or C ommand is not allowed! if the command
is refused, or Command time has run out! if no response has been given.
5. Press ESC to return to another command or the Default screen.
Command Description
RESET ALARM
Resets all faults.
INVERTER ON
Makes a secure transfer from static bypass operation to
normal operation. The command will be refused if the
bypass and inverter conditions are not synchronized.
INVERTER OFF
Makes a s ecure transfer from normal operation to static
bypass operation. The command will be refused if the
bypass and inverter conditions are not synchronized.
FORCE LO AD TRANSFER TO INVERTER
Forces the UPS to transfer from static bypass operation
to normal operation whereby the bypass condition is
ignored. A short load drop may occur.
FORCE LOAD TRANSFER TO BYPASS Forces the UPS to transfer from normal operation to
static bypass operation whereby the bypass condition is
ignored. A short load drop may occur.
990-3619B-001
MGE™ Galaxy™ 300 and MGE™ Galaxy™ 300i Operation
29