Note: As mentioned above, it is possible to change several settings under the
PERSONALIZATION menu without having to escape and reenter the menu. Before you
escape to the PERSONALIZATION menu, the UPS will save all new settings by the
prompts:
Save new settings? (press ENTER to confirm or ESC to return to the previous screen(s)).
Saving settings......
Setting success!
Save new settings?
Saving settings......
Setting success!
Note: If the Setting failed! prompt appears, wait three seconds before the display returns to
the PERSONALIZATION menu, and then try again.
Setting the UPS Operation Mode
WARN ING: Please be aware that this procedure does not describe how to turn f rom
one operation mode into another w hen the U PS is up running. See “Operation Modes“
instead.
1. From the Default screen, press ENTER.
2. Go to SETTINGS by using the UP/DOWN
navigation keys and press ENTER.
SETTINGS
3. Go to PERSONALIZATION by using
the UP/DOWN navigation keys and press
ENTER.
PERSONALIZATION
4. Go to UPS OPERATION MODE by using
the UP/DOWN navigation keys and press
ENTER.
UPS
OPERATION MODE
5. Select Normal mode, Parallel mode,or
Frequency converter mode by using the
UP/DOWN navigation keys and press
ENTER.
NORMAL MODE
Setting the Output Voltage
Note: The procedure for setting the OUTPUT VOLTAGE isthesameasdescribed
under “Setting the UPS Operation Mode“ except for steps 4 and 5 where you m ust select
OUTPUT VOLTAGE and values 220 V, 230 V or 240 V.