Overview
Display Interface
The eight LEDs to the left of the display screen (1-8) indicate the operational status of the UPS. The four
navigation keys at the bottom right of the interface (10-12) are used to select and open menu i tems, access
information, and change UPS parameters. The two buttons at the upper right of the interface (13- 14)
are used to turn in and out of normal operation.
LEDs
Note: The flow diagram (1-5) shows the electrical power flow and gives t he status of main
functions. The LEDs are:
green when the function is active
red when a fault has occurred in the f unction
OFF when the function is inactive
* indicates double-conversion mode.
1PFC
Green: Power Factor Correction (PFC) works on normal AC input.
Red: An AC normal fault, DC BUS fault, or major PFC fault has
occurred.
OFF: The PFC is not working.
2
INVERTER
Green: The inverter is operating.*
Red: A major fault in the inverter or a fault in the static switch
has occurred.
OFF: The inverter is OFF.*
3 LOAD
Green: The inverter supports the load* or the load is supported
by the AC bypass source.
Red: The inverter is not connected to the load* and the load i s not
supported by the AC bypass source or QOP is open.
OFF: The maintenance bypass breaker Q3BP is ON (closed).
4 BATTERY
Green: The U PS is in battery operation.
Red: A major fault in the battery or the charger has occurred, or the
battery circuit breaker is OFF.
OFF: The batteries are charging or ready to supply the load if the
AC power fails or battery present configuration is absent.
990-3619B-001
MGE™ Galaxy™ 300 and MGE™ Galaxy™ 300i Operation
1