APC MGE Galaxy 3500 40kVA 400V, Start-Up 5X8 Specifications Page 11

  • Download
  • Add to my manuals
  • Print
  • Page
    / 40
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 10
5MGE Galaxy 3500 10-40 kVA 380/400/415 V Quick Reference
AC Output
Specifications
380 V, 400 V, and 415 V
380 V, 400 V, and 415 V 3:1
10 kVA 15 kVA 20 kVA 30 kVA 40 kVA
380 V 400 V 415 V 380 V 400 V 415 V 380 V 400 V 415 V 380 V 400 V 415 V 380 V 400 V 415 V
Connection type 5-wire (3PH + N + PE)
Output capacity
150% for 1 minute (normal operation)
125% for 10 minutes (normal operation)
150% for 1 minute (battery operation)
125% for 10 minutes (battery operation)
110% continuous (bypass operation)
800% for 500 ms (bypass operation)
Voltage tolerance +/- 20% (304-477 V) at full load
Nom output current (A) 15.2 14.4 13.9 22.8 21.7 20.9 30.4 28.9 27.8 45.6 43.3 41.7 60.8 57.7 55.6
Output frequency (sync to mains) 47-53 Hz for 50 Hz nominal
Slew rate (Hz/Sec) 0.25-1
Total Harmonic Distortion (THD)
< 1.5% linear
< 3.5% non-linear
Output power factor 0.8
Dynamic load response +/- 5%
Output voltage regulation +/- 1%
15 kVA 20 kVA 30 kVA 40 kVA
220 V 230 V 240 V 220 V 230 V 240 V 220 V 230 V 240 V 220 V 230 V 240 V
Connection type 3-wire (1PH + N + G)
Output capacity
150% for 1 minute (normal operation)
125% for 10 minutes (normal operation)
150% for 1 minute (battery operation)
125% for 10 minutes (battery operation)
110% continuous (bypass operation)
800% for 500 ms (bypass operation)
Voltage tolerance +/- 20% (304-477 V) at full load
Nom output current (A) 68.4 65.0 62.6 91.2 86.6 83.5 136.7 129.9 125.2 182.3 173.2 166.9
Output frequency (sync to mains) 47-53 Hz for 50 Hz nominal
Slew rate (Hz/Sec) 0.25-1
Total Harmonic Distortion
(THD)
< 1.5% linear
< 3.5% non-linear
Output power factor 0.8
Dynamic load response +/- 5%
Output voltage regulation +/- 1%