MGE Galaxy 3500 10-40 kVA 380/400/415 V Quick Reference28
Input and Output Contacts
Pin connections J106 (UPS)
Pin connections J106 (UPS)
8) Exernal charging control return
7) External control of charging
6) Q3 active return
5) Q3 active
4) Battery measurement supply*
3) Battery unit quantity*
2) Max. battery temperature*
1) Battery measurement return*
* Should be used with MGE Galaxy 3500 XR Enclosures
J106
Q3 switch
Charging control
switch
J200 (XR
Batteries)
Pins 7 and 8 are for external charge control. When 7 and 8 are
closed, the UPS charges batteries with a pre-defined
percentage (0-25-50-75-100%) of the maximum charging
power. To be used in generator applications, or if special
codes require control of charging.
When Q3 is closed, signals are fed back to the UPS
controller.
Pins 5 and 6 are for external maintenance bypass Q3
(auxiliary switch N/C type).
When Q3 is closed, signals are fed back to the UPS controller
(see Q3 drawing).
Pins 1 to 4 are for battery measurement (only applicable to
MGE Galaxy 3500 XR Battery Enclosures - see J200 drawing).
Page view 33