APC Smart-UPS VT Installation Manual Page 17

  • Download
  • Add to my manuals
  • Print
  • Page
    / 44
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 16
Smart-UPS
®
VT Maintenance Bypass Panel w Power Distribution, 10-30kVA, 208V - 990-4199B 11
Considerations
Environmental
The MBP should be kept in a climate-controlled environment having a temperature range of 0°
to 40°C [32° to 104°F] and a relative humidity of 0% to 95%, non-condensing.
The MBP must be protected at all times from excessive moisture, construction dirt, corrosive
elements, and other contaminants.
The floor surface on which the MBP rests must be firm and level, and the total weight of the
installed unit(s) must not exceed limitations for floor loading.
Spacing
There should be a minimum of 36 inches [914mm] clearance directly in FRONT of the MBP to
accommodate installation, servicing, and access to the panel board (if included).
There should be a minimum of 36 inches [914mm] clearance directly BEHIND the MBP to
accommodate installation, servicing, and access to the rear of the panel board (if included).
There should be a minimum of 20 inches [508mm] clearance ABOVE the MBP to
accommodate ventilation.
36”
[914]
36”
[914]
20”
[508]
FRONT
BACK
TOP