28 Smart-UPS
®
VT Maintenance Bypass Panel w Power Distribution, 10-30kVA, 208V - 990-4199B
Operation
The MBP with Power Distribution supports four (4) modes of UPS operation: 1) Normal, 2) Battery
Back-up, 3) Static Bypass, and 4) Bypass.
The process of changing from one operational mode to another requires a series of automated and
manual tasks. Automated tasks are initiated from the user interface at the front of the UPS and may
require switches on the MBP to be turned ON or OFF, depending on the operational mode.
A switch can be locked in place by pressing down on its red lever and then applying a locking device
to the exposed holes. The MBP is shipped with its switches in the OFF position (graphic A).
Normal operating mode
To enter normal operating mode (graphic B), first switch Q2 ON and then switch Q1 ON. Q3 remains
OFF. The heavier line shows the flow of utility power through Q1, the UPS, and Q2.
See also
Refer to the Smart-UPS VT 10-30kVA Operation Manual (p/n 990-1599) for an
overview of the functionality of the user interface.
AC
Input
UPS
Static
Bypass
Load
Panel
Q1
UPS Input
Q3
Bypass
Q2
UPS Output
Input
Output
O OFF
I ON
O OFF
I ON
O OFF
I ON
AC
Input
UPS
Static
Bypass
Load
Panel
Q1
UPS Input
Q3
Bypass
Q2
UPS Output
Input
Output
O OFF
I ON
O OFF
I ON
O OFF
I ON
A
B