Floor loads (figure 5)
Cubicle footpads
Fig. 5
33 33
33
3333
33
four 60 mm dia.
footpads with
12 mm average
depth holes for
M16 anchor bolts
736
cubicle width
less 66 mm
front
rear
Cubicle layout on false floor or normal floor (figures 6, 7, 8)
Layout for a single-unit UPS with one battery cubicle
Fig. 6
Layout for a single-unit UPS with several battery cubicles
Fig. 7
battery cubicle
50
front
80
rear
>25
rectifier-inverter cubicle
spacing uprights
cutouts necessary for
cable entry from underneath
a false floor:
200 mm x (W – 160 mm)
800
can equal 0
> 1000
location
of trench
under cubicles
(if applicable)
cubicle width W
(see table)
cubicle width W
(see table)
the floor supports the weight of each
cubicle via the four 60 mm diameter
pads at the bottom of the feet screwed
into the corners of the frame;
the exact locations of the footpads
are indicated in the figure;
normally the cubicles do not have to
be secured to the floor; the footpads
nevertheless have holes with an
average depth of 12 mm designed for
the fitting of M16 anchor bolts;
to determine the stresses applied by
the cubicle feet on the floor, divide the
cubicle weight (see the first 3 tables of
this manual) by the total area of the 4
footpads (110 cm
2
).
the cubicles can be installed directly
up against the rear wall;
an overall clearance of 400 mm must
be left above the entire surface of the
cubicles for ventilation;
a side clearance of 25 mm is
provided by the vertical bars on the
sides of the cubicles to allow door
opening. For cubicles mounted side by
side, the two adjacent bars ensure an
inter-cubicle clearance of 50 mm;
a minimum clearance of 1000 mm is
required in front of the cubicles to allow
complete opening of the doors and
easy access for maintenance work
(replacement of subassemblies);
for extended battery backup times or
high output systems, the UPS may
have several battery cubicles (see the
table at the end of the previous
chapter). If this is the case, install the
battery cubicles on the left side of the
rectifier-inverter cubicle with the cubicle
containing the battery circuit breaker
QF1 closest to the rectifier-inverter
cubicle (figure 7);
when an auxiliary cubicle is included
in the UPS, it should be installed to the
left of the battery cubicle(s);
connection via the bottom
The connection cables may be run in
three ways:
in a cable trench running underneath
the front of the cubicles (see trench
dimensions and layout in figure 6),
under a false floor.
A cutout must in this case be made in
the floor for cable entry (see figure 6 for
dimensions),
Installation (cont.)
battery cubicle 2
front
rear
rectifier-inverter cubicle
battery cubicle 1
containing battery
circuit breaker QF1