Page 36 - 6739381EN/JD
Cubicle mounting and connection for 600kVA UPSs
Cubicle mounting
Gusset plates have been fitted to the
top corners on all four sides of the
cubicles to provide reinforcement for
transportation.
prior to joining the two cubicles,
remove the two gussets from the right
side of the left cubicle;
move the cubicles to their operating
location;
adjust the front foot pads so that the
cubicles are vertical and their doors
aligned;
remove the top panel on the left side
of the right cubicle for access to the
side gussets (see figure opposite);
remove the gussets 1 on the front
of the left cubicle;
remove and turn around the double
gussets 2 on the right cubicle and
use them to bolt the two cubicles
together.
Internal connections between
cubicles
removal of inverter leg no.6 is
recommended prior to bolting fish-
plates L+ and L–:
first remove the two fuses and the
two cables connected to the leg,
then pull the leg out;
bolt fish-plates L+ and L–;
refit inverter leg no 6;
intended only for transportation, the
front gussets do not need to be refitted;
bolt cables L1, L2, L3 and N (4 x 2)
coming from the right cubicle to the
terminals marked L1, L2, L3 and N
respectively, in the left cubicle;
connect the earth strap to the front
uprights of both cubicles;
connect the connectors marked
XF281 to XF285 on the five ribbon
cables coming from the left cubicle to
connectors XM281 to XM285
respectively on the interface board
located on the left side of the right
cubicle;
connect the connectors marked
XF01 to XF06 (XF01 to XF07 for
parallel UPSs) on the control wires
coming from the left cubicle to
connectors XM01 to XM06 (XM01 to
XM07 for parallel UPSs) on the plate on
the left side of the right cubicle.
inverter leg no. 6 fuses and cables
to be disconnected
interface board
and connection
plate for control
wires
fish-plates
to be
bolted
cables to be
connected
right cubicleleft cubicle
L
L+
L3
L2
L1
N
earthing connection
between cubicles
single gusset
to be
removed
double gusset
to be
turned around
left cubicle right cubicle
A B
1
2
Appendix (cont.)