USERS GUIDE
network management card
73
Utility Line Settings
This Configuration menu option is available to all UPS models except a
Silcon UPS. The available settings differ based on the
UPS model.
Smart-UPS or Matrix-UPS. Not all Utility Line settings are available for
all Smart-UPS and Matrix-UPS models, and each settings selections can
differ from
UPS-to-UPS.
Setting Definition
Output Voltage Defines the nominal
AC voltage level for the UPS output.
High Transfer
Voltage
Defines the upper limit of acceptable input voltage. When the
input reaches this value, the
UPS will go on battery
(Matrix-UPS) or start using its
AVR Trim feature (Smart-UPS).
Low Transfer Voltage
Defines the lower limit of acceptable input voltage. When the
input reaches this value, the Smart-UPS will start using its
AVR
Boost feature, or go on battery, if it does not have this feature.
Note: For a Matrix-UPS, this setting cannot be changed.
Vout Reporting
(Matrix-UPS)
Defines how Matrix-UPS scales its output voltage readings.
Sensitivity
Defines how sensitive the
UPS will be to distortions in the input
voltage.
Note: Matrix-UPS uses an Automatic setting.