110 Installation Guide Silcon DP300E 208V/480V 10-80 kVA
7OY0002 US rev. 04
Options/Accessories
Centres for fixing holes
in rear of enclosure
B
A
4 x Ø 10mm on 720 x 650
8.10.3 Mounting and Connection
NOTE:
All external cable dimensions
are recommended.
Please refer to local legal
provisions.
NOTE:
Terminal for Equipment
Grounding Conductor is
marked
NOTE:
Ensure correct polarity at
connection of DC cables.
NOTE:
Grounding, please refer to local
legal provisions.
Type For
a)
Ext. DC Ext. Dimen- Fixing Weight
System Conduc- Equipment sions Centres [kg/lbs]
tor Grounding HxWxD AxB
[AWG] Conductor [mm] [mm
2
]
[AWG]
MCCB- 10kVA 480V 10 10 450x400 350x285 13/28.6
310E-480 x125
MCCB- 15kVA 480V 6 10 450x400 350x285 13/28.6
320E-480 20kVA 480V x125
MCCB- 30kVA 480V 2 8 450x400 350x285 13/28.6
340E-480 40kVA 480V x125
MCCB- 60kVA 480V 2 8 450x400 350x285 13/28.6
360E-480 x125
MCCB- 80kVA 480V 1/0 6 750x550 648x448 24/52.8
380E-480 x175
MCCB- 10kVA 208V 6 10 450x400 350x285 13/28.6
310E-208 x125
MCCB- 15kVA 208V 2 8 450x400 350x285 13/28.6
320E-208 20kVA 208V x125
MCCB- 30kVA 208V 1/0 6 750x550 648x448 24/52.8
340E-208 40kVA 208V x175
MCCB- 60kVA 208V 4/0 6 750x550 648x448 24/52.8
360E-208 x175
MCCB- 80kVA 208V 300 4 750x550 648x448 24/52.8
380E-208V kcmil x175
a) Cable sizes refer to US National Electric Code, Table 310-16, cables rated 75˚C/167˚F at max.
40˚C/104˚F ambient.
As regards recommended cable lugs and crimping tool, see section 4.1.4.
8.10.3.1 Mounting and Connection
DC-cables rated 600V, unless otherwise stated.
DC-cables rated 1000V on 480V systems from MCCB-box to UPS.