APC 10-40kW 208/480V Installation Guide Page 28

  • Download
  • Add to my manuals
  • Print
  • Page
    / 119
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 27
28 Installation Guide Silcon DP300E 208V/480V 10-80 kVA
7OY0002 US rev. 04
Remarks:
X003 and X004, auxiliary contacts:
When switching Q001, Q002, MCCB1, and MCCB2 from “ON” to “OFF” the auxiliary
contacts have to give a signal before the corresponding mains switch is opened.
When switching from “OFF” to “ON” the auxiliary contact has to be activated with
max. 0.5 sec. delay from the corresponding main switch.
When switching Q003 from “OFF” to “ON” the auxilliary contact has to give a signal
before Q003 is closed. When switching from “ON” to “OFF” the auxilliary contact has
to be activated with max. 0.5 sec. delay.
Connection
4.2.2 Connections
NOTE:
When installing UPS systems
with Emergency Power Off
(EPO) all input sources must be
provided with disconnecting
device when activating EPO.
white
black
Page view 27
1 2 ... 23 24 25 26 27 28 29 30 31 32 33 ... 118 119

Comments to this Manuals

No comments