44 Installation Guide Silcon DP300E 208V/480V 10-80 kVA
7OY0002 US rev. 04
Programming parameters
Parameter Setting* Comments
Isolation trafo mains YES, NO YES if optional input isolation transformer is
present
Isolation trafo output YES, NO YES if optional output isolation transformer is
present
Delta soft start time 1, 10, 20, Input current switching in ramp function.
40 secs. Higher values used together with smaller/
unstable diesel generators
External SSW present YES, NO YES for systems with external static bypass
switch
Normal charge voltage Setting of float charge voltage at 20°C /68°F
(Aut. compensation for deviations)
Boost charge voltage Setting of boost charge voltage at 20°C /68°F
(Aut. compensation for deviations)
Low battery warning Warning for discharged battery
Low battery shut down Switches off the system at min. permissible
battery voltage
Synchronization 0.25, 0.5, 1 Synchronisation speed. Higher values used
2, 4 Hz/sec with very unstable mains frequencies
High battery temperature 15-40°C Alarm for too high battery ambient
/59-104°F temperature
35°C
/95°F
Common fault delay 0, 10, 20 Delay before the common fault alarm relay is
30 secs. activated
Reset operation mode YES, NO YES resets system locked in bypass or battery
lock operation mode caused by system failures
(Only for service personnel)
Expected back-up 0,1-999,9 Expected back-up time for UPS in minutes,
time [min.] 5,0 when running at 100% ohmic load.
Time used by the ABM**
Battery capacity 0,1-999,9 Total battery capacity in Ah.
in [Ah] 7,0 Setting used by the ABM**
Highest station address 2-9 Highest station address in parallel system
Station address 1-9 Station address in parallel system
Advanced power None Only used in parallel system.
management (APM) Off: Advanced power management disabled.
Parallel +1: Redundant operation with all units
in operation.
Redundant +1: Redundant operation with
one unit being inactive in parallel system
APM test mode active YES, NO YES, if APM test mode is active
Battery connection Common, Common if common battery is used in parallel
Separate system. Separate if separate battery is used
6.3 Programming of system configuration parameters
The system configuration parameters are protected by a password because most of
them are critical for correct operation of the system. Wrong programming can for
example destroy the battery or cause loss of output voltage during opera-
tion!!
6.3.1 System configuration parameters
* Text in bold letters are the factory standard setting
** Advanced Battery Monitor
NOTE:
Common battery pack is a
technical possibility.
However, APC recommend
separate battery pack due to a
higher safety degree in con-
nection with redundant/parallel
operation.
The UPS system is prepared
for both solutions.