96 Installation Guide Silcon DP300E 208V/480V 10-80 kVA
7OY0002 US rev. 04
Options/Accessories
8.8.5 Recommended cable lugs and crimping tool types
See section 4.1.4.
8.8.6 Isolation transformer - Diagram Delta-WYE configuration (Dyn11)
8.8.7 Grounding the isolation transformer
8.8.7.1 System grounding
Provisions have to be made as follows:
a. If not mounted, the bonding jumper is mounted between output terminal X002:N
and X002:E.
No bonding jumper is required on the Silcon DP360E and DP380E, 208V insola-
tion transformer since the X002:N and X002:E is a common terminal.
b. The output terminal X002:E, also marked “Grounding Electrode Terminal” is
connected by a grounding electrode conductor to a local grounding electrode per
NEC 250-26.
8.8.7.2 Equipment grounding
a. Terminal marked is intended for equipment grounding.
L2
L3
G
L1
L2
L3
G
155˚C
L1
Input
X001
Output
X002
Temp.
Alarm
X003
1
2
N
E