62 Installation Guide Silcon DP300E 208V/480V 10-80 kVA
7OY0002 US rev. 04
Options/Accessories
EMERGENCY (UPS not alive)
1. Turn the input switches (Q001) to position “0“.
2. Turn the output switches (Q002) to position “0“.
3. Turn the output switch (Q004) to position “0”.
4. Change any released system input fuse(s).
5. Turn the bypass switch (Q003) to position “1“.
9. Open the front door and press the red “OFF”
push-button in any of the systems.
The acoustic alarm sounds for 30 secs.*
Repeat for (all) other system(s)
10. Turn all input switches (Q001) to position “0“
The red alarm LED below the display lights and
the acoustic alarm sounds for 30 secs.
* The acoustic alarm can be reset by the
key
**System OFF**
Display shows