89Installation Guide Silcon DP300E 208V/480V 10-80 kVA
7OY0002 US rev. 04
Options/Accessories
8.8 Isolation Transformer Module
Introduction.
The isolation transformer module is used in following mentioned configurations:
1. Between mains supply and UPS input, when a 3-phase Delta-service, phase
or midpoint of 2 phases grounded, is available.
2. Between mains supply and UPS input, when galvanic isolation is required.
3. Between UPS output and load, when galvanic isolation is required.
The isolation transformer is configured as Delta-WYE with accessibel neutral
(Dyn11).
Isolation For UPS System
Transformer Type
10kVA - 480V DP310E - 480V
15kVA - 480V DP315E - 480V
20kVA - 480V DP320E - 480V
30kVA - 480V DP330E - 480V
40kVA - 480V DP340E - 480V
60kVA - 480V DP360E - 480V
80kVA - 480V DP380E - 480V
10kVA - 208V DP310E - 208V
15kVA - 208V DP315E - 208V
20kVA - 208V DP320E - 208V
30kVA - 208V DP330E - 208V
40kVA - 208V DP340E - 208V
60kVA - 208V DP360E - 208V
80kVA - 208V DP380E - 208V
8.8.1 Requirement on the installation site
The isolation transformer is designed with all parts accessible from front or top, and
cable entries from bottom. The isolation transformer can be placed close to walls,
only free space for front door opening has to be ensured. Sufficient cooling has to be
ensured by a free space of min. 19.68 in./500mm above the ventilation slots in the
top cover. Avoid placing the isolation transformer in direct sunlight.