51Installation Guide Silcon DP300E 208V/480V 10-80 kVA
7OY0002 US rev. 04
Options/Accessories
Parallel operation alarms.
General.
If alarms concerning the parallel operation communication arise all parallel opera-
tion functions being controlled by the advanced management will be inactive. If the
advanced parallel operation functions are inactive, “only” the simple hardware
control of parallel operation, which controls load sharing, operation mode, etc., is
left.
Alarm texts conc. parallel operation.
In case of fault in parallel operation the following alarm will be active in the alarm
stack:
“Communication to parallel IF lost”.
Other reasons for parallel operation alarm.
When a system is isolated (PSU OFF) due to service this fault will as well arise
on the systems still operating. The reason is that the isolated system is no longer
to be found (active) in the parallel system. The fault can only be deleted by
turning on the PSU or by reprogramming the station addresses on all systems so
that the sequence is: 1 to max_number_system.