APC MGE 6739380EN/JC User Manual Page 17

  • Download
  • Add to my manuals
  • Print
  • Page
    / 50
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 16
6739380EN/JC - Page 17
I
+–
!
!
O
beep...beep...
1
I
+–
!
!
O
2
I
+–
!
!
O
3
I
+–
!
!
O
4
I
+–
!
!
O
5
I
+–
!
!
O
6
Buzzer 1
The buzzer sounds in the following
situations:
load supplied by Mains 2;
load on battery;
operating problems.
It beeps at a low decibel level and slow
rate for minor problems and when the
load is supplied from battery power.
When the "low battery shutdown
imminent" warning is received, the
beeps
increase in decibel level and rate.
Finally, if the inverter shuts down, the
beep is loud and continuous. A buzzer
reset button is located on the hidden
control panel. If the buzzer is reset, a
higher level alarm will set it on again.
"Load not protected" light
This red light 2 signals that:
the load is supplied by Mains 2
following inverter shutdown (initiated by
the user or by a protective device or a
sudden overload) or the opening of the
inverter output switch Q5N;
battery circuit breaker QF1 has
opened, thus making battery power
unavailable.
Note:
In a parallel system, this light concerns
only the specific UPS. The load may still
be protected by the other lines.
Note:
In parallel systems, this light concerns
only the specific UPS.
The load may not be protected if it
depends on the other lines. It is
necessary to take into account all the
"load protected" lights 5 for the
different system lines or the light on the
control panel of the Static Switch
Cubicle, if it exists.
"Inverter on" button
This green button 6 is used to locally
start the inverter. When it is pushed,
the green "load protected" light 5
blinks for 3 seconds, indicating that the
start-up order has been received. When
the inverter has synchronized with
Mains 2, it supplies the load and the
green "load protected" light 5
remains on. The load is supplied by the
UPS and the system is functioning
normally. If the transfer to Mains 2
conditions are not correct (Mains 2
voltage, frequency or phase conditions
outside tolerances), the inverter will not
start and the system awaits a special
order (see the "Hidden control panel"
section).
Note:
for modular UPSs with external
maintenance bypass or parallel UPSs
with SSC, transfer of the load to the
inverters takes place only when the
number of operating lines required to
supply the load has been reached;
for frequency converters, inverter
start-up must take place with the load
off or drawing a quantity of power equal
to or less than that supplied by a single
UPS.
"Operating problem" light
This orange light 3 signals an
operating problem or an environment
fault, however the load is still supplied
by the inverter.
operating problems:
static switch ventilation fault,
static switch control system fault;
environment faults:
battery temperature outside
tolerances,
overload greater than 5%,
Mains 2 up but with voltage,
frequency or phase characteristics
outside tolerances with regards to the
inverter.
"Battery operation" light
This blinking orange light 4 signals
that the load is on battery power
following:
a Mains 1 outage or voltage drop;
insufficient power on Mains 1, for
example power supplied by an engine
generator set requiring additional
battery power;
battery problem.
"Load protected" light
This green light 5 signals that the
load is supplied by the inverter and that
the specified battery time is available
in the event of a Mains 1 outage. In
short, it signals that the system is
operating normally.
Control panel (cont.)
Page view 16
1 2 ... 12 13 14 15 16 17 18 19 20 21 22 ... 49 50

Comments to this Manuals

No comments